INSTALLATION INSTRUCTIONS
Blank Patch Panel for Category 6A FTP 10G, 24-Port, 1 RMS
Step 1: Mount the patch panel to the rack using four (4) #12-24 rack
screws.
Step 2: Install the cable management bar onto the rear of the patch
panel. Align the tabs on both sides and push the bracket downward until
fully seated. Use the grounding screw (included) to attach grounding wire
(not included).
Step 3: Insert the CAT 6A FTP modular connector into a port on the patch
panel. Note: Inspect the connector to ensure it is fully seated, and the
front is ush with the panel.
Step 4: Secure the cable to the cable management bar using a nylon
cable tie. Note: A slot on the bar allows you to insert and secure the tie.
Rack
Slot
Grounding screw
Cable tie